This is a smart rs485 temperature
sensor. The housing of the Modbus temperature sensor is made of abs plastic
with vents, and there is a slot on the back, which can be directly installed on
the rail. sensor adopts standard Modbus-RTU communication protocol, supports
Kingview, 3D force control, MCGS Kunlun configuration software configuration
screen, PLC, user-developed platform.
Power supply (default): 10-30V DC
Power consumption: 0.3W
A precision: Humidity: ±2%RH (5%~95%RH, 25℃), temperature: ±0.4℃ (25℃)
B quasi-accuracy:(Default) Humidity: ±3%RH (5%RH~95%RH, 25°C),
temperature: ±0.5°C (25°C)
Transmitter circuit working temperature: -40℃~+60℃, 0%RH~80%RH
Communication protocol: Modbus-RTU communication protocol
Output signal: 485 signal
Temperature display resolution: 0.1℃
Humidity display resolution: 0.1%RH
Temperature and humidity refresh time: 1S
Long-term stability: temperature ≤0.1℃/y humidity ≤1%RH/y
Response time: Temperature ≤15s (1m/s wind speed) Humidity ≤4s (1m/s
wind speed)
Parameter setting: through software setting
Place of origin: China
Communication protocol
1. Basic
communication parameters
Code |
8 bit binary system |
Data Bit |
8 bit |
Odd-even Revi-sion Bit |
None |
Stop Bit |
1bit |
Incorrect Revis-ion |
CRC(Redundant cyclic codes) |
Baud Rate |
2400bit/s, 4800bit/s, 9600
bit/s options, the factory default 4800bit/s |
2. Data
frame format definition
Using
Modbus-RTU communication protocol, the format is as follows:
Initial structure ≥4 bytes of time
Address code = 1 byte
Function code = 1 byte
Data area = N bytes
Error check = 16-bit CRC code
Time to end structure ≥ 4 bytes
Address code: the address of the transmitter, which is unique in the
communication network (factory default 0x01).
Function code: the function instruction of the command sent by the host, this
transmitter only uses the function code 0x03 (read register data).
Data area: The data area is the specific communication data, pay attention to
the high byte of the 16bits data first!
CRC code: two-byte check code.
Host
query frame structure:
Address
Code |
Function
Code |
Register
Origin Address |
Register
Length |
Revision
Code in Low Position |
Revision
Code in High Position |
1byte |
1byte |
2bytes |
2bytes |
1byte |
1byte |
Slave
response frame structure:
Address
Code |
Function
Code |
Effectiveness
Byte NO. |
Data
Area One |
Data
Area Two |
Data
Area N |
Revision
Code |
1byte |
1byte |
1byte |
2bytes |
2bytes |
2bytes |
2bytes |
3.
Register address
Register
Address |
PLC or
Configuration Address |
Content |
Operation |
0000 H |
40001 |
Humidity |
Read only |
0001 H |
40002 |
Temperature |
Read only |
Showing 1 to 2 of 2 entries
4.
Communication protocol example and explanation
Low Cost Temperature Humidity Transmitter RS485